72 Managing Cooling options
4 - CONFIGURATION
Managing Cooling options
To configure cooling options
1. Swipe left from the Home screen.
2. On the Quick access screen, tap > Advanced > Cooling.
The Cooling Options screen appears.
Cooling
Recovery
Setpoint Ramp 0 -20°F/hr (Default
6°F/hr
When outside air temperature is available,
the effective cool ramp rate is changed as
the outdoor air temperature changes. When
the outdoor air temperature is at the
minimum cool ramp rate temperature (e.g.
90°F) and above, the effective cool ramp
rate is at the minimum cool ramp (e.g. 2
Δ°F/hr). When the outdoor air temperature
falls, the cool ramp rate is lowered until the
maximum cool ramp temperature (e.g.
70°F) is reached or above, the effective cool
ramp is at the maximum cool ramp rate (e.g.
6
Δ°F/hr).
Heating
Recovery
Setpoint Ramp 0 -36°F/hr (Default
8°F/hr
When outside air temperature is available,
the effective heat ramp rate is changed as
the outdoor air temperature changes. When
the outdoor air temperature is at the
minimum heat ramp rate temperature (e.g.
0°F) and below, the effect heat ramp rate is
at the minimum heat ramp (e.g. 2
Δ°F/hr).
When the outdoor air temperature is at the
maximum heat ramp temperature (e.g.
60°F) and above, the effective heat ramp is
at the maximum heat ramp rate (e.g. 8
Δ°F/
hr).
Table 23: Setpoint options
Operation Configuration
Type
Range Description

Table of Contents

Other manuals for Honeywell TC300

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell TC300 and is the answer not in the manual?

Honeywell TC300 Specifications

General IconGeneral
BrandHoneywell
ModelTC300
CategoryThermostat
LanguageEnglish

Related product manuals