18 TR50 - User Guide
Out of Range reading
Alarm set values
LCD Brightness
4.4.5.1 Input Points
4.4.5.2 Temperature Configuration Points
Point Name
BACnet
Instance
Read/
Write
Type Range
SS_AI_SensorReading_Temp 1 Read Analog Input
32-122 (
o
F)
0-50 (
o
C)
SS_AI_SensorReading_Humi 2 Read Analog Input 0-100 (%)
SS_AI_SensorReading_CO
2
3 Read Analog Input 0-9999 (ppm)
SS_AI_SensorReading_PM2.5 4 Read Analog Input
0-5000 (ug/m
3
)
SS_AI_SensorReading_TVOC 5 Read Analog Input 8-2820 (ppb)
16-5640 (ug/m
3
)
SS_AI_AIR_QUALITY_SCORE 6 Read Analog Input 0-100
SS_AI_SensorReading_PM1.0 7 Read Analog Input
0-5000 (ug/m
3
)
SS_AI_SensorReading_PM10 8 Read Analog Input
0-5000 (ug/m
3
)
Point Name
BACnet
Instance
Read/
Write
Type
Default
Value
Range
CfgAlarmTempLowLimit 1 R/W Analog
Value
65(
o
F)
18(
o
C)
32
o
F <= PRESENT VALUE of
cfgAlarmTempLowLimit <=
PRESENT VALUE of
cfgAlarmTempHighLimit
0
o
C <= PRESENT VALUE of
cfgAlarmTempLowLimit <=
PRESENT VALUE of
cfgAlarmTempHighLimit
CfgAlarmTempHighLimit 2 R/W Analog
Value
86(
o
F)
30(
o
C)
PRESENT VALUE of
cfgAlarmTempLowLimit
<= PRESENT VALUE of
cfgAlarmTempHig Limit<=
122
o
F
PRESENT VALUE of
cfgAlarmTempLowLimit <=
PRESENT VALUE of
cfgAlarmTempHighLimit<=
50
o
C
CfgAlarmTempDeadband 3 R/W Analog
Value
1(
o
F)
1(
o
C)
0(
o
F) <= PRESENT_VALUE of
cfgAlarmTempDeadband
0(
o
C) <= PRESENT_VALUE of
cfgAlarmTempDeadband
CfgAlarmTempTimeDelay 4 R/W Analog
Value
60(s) 0(s) <= PRESENT_VALUE of
cfgAlarmTempTimeDelay