TR50 - User Guide 19
4.4.5.3 Humidity Configuration Points
SS_MV_OutofRange_Temp 1 R/W Multi
State
Value
1 1: Normal
2: Off normal
CfgTempSensorOffset 281 R/W Analog
Value
0
-9 to 9 (
o
F)
-5 to 5 (
o
C)
CfgAlarmTempLimitEnable 21 R/W Multi
State
Value
4 1:Temp Low Limit And High
Limit Disable
2:Temp Low Limit Enable
3:Temp High Limit Enable
4:Temp Low Limit And High
Limit Enable
cfgDisplayUnitTemp 101 R/W Multi
State
Value
1
1: Degrees Fahrenheit (
o
F)
2: Degrees Celsius (
o
C)
Point Name
BACnet
Instance
Read/
Write
Type
Default
Value
Range
Point Name
BACnet
Instance
Read/
Write
Type
Default
Value
Range
CfgAlarmHumiLowLimit 51 R/W Analog
Value
10(%) 0
<= PRESENT VALUE of
cfgAlarmHumiLowLimit
<= PRESENT VALUE of
cfgAlarmHumiHighLimit
CfgAlarmHumiHighLimit 52 R/W Analog
Value
80(%) PRESENT VALUE of
cfgAlarmHumiLowLimit
<= PRESENT VALUE of
cfgAlarmHumiHighLimit
<=100
CfgAlarmHumiDeadband 53 R/W Analog
Value
2
0 <= PRESENT VALUE
ofcfgAlarmHumiDead
band
CfgAlarmHumiTimeDelay 54 R/W Analog
Value
60(s)
0 <= PRESENT VALUE of
cfgAlarmHumiTimeDelay
SS_MV_OutofRange_Humi 2 R/W Multi State
Value
1 1: Normal
2: Off normal
cfgAlarmHumiLimitEnable 22 R/W Multi State
Value
4 1:Humidity Low Limit
And High Limit Disable
2:Humidity Low Limit
Enable
3:Humidity High Limit
Enable
4:Humidity Low Limit
And High Limit Enable
cfgHumiSensorOffset 282 R/W Analog
Value
0 -10 to 10