20 TR50 - User Guide
4.4.5.4 CO
2
Configuration Points
Point Name
BACnet
Instance
Read/
Write
Type
Default
Value
Range
CfgAlarmCO
2
HighLimit 101 R/W Analog
Value
1000(ppm)
0
<= PRESENT VALUE of
cfgAlarmCO
2
HighLimit
<= PRESENT VALUE of
cfgAlarmCO
2
HighHigh
Limit
CfgAlarmCO
2
HighHighLimit 102 R/W Analog
Value
1400(ppm)
PRESENT VALUE of
cfgAlarmCO2HighLimit
<= PRESENT VALUE of
cfgAlarmCO
2
HighHigh
Limit <= 9999
CfgAlarmCO
2
Deadband 103 R/W Analog
Value
100 0 <= PRESENT VALUE of
cfgAlarmCO
2
Deadband
CfgAlarmCO
2
TimeDelay 104 R/W Analog
Value
60(s) 0 <= PRESENT VALUE of
cfgAlarmCO
2
TimeDelay
cfgCO
2
SensorOffset 283 R/W Analog
Value
0 -1000 <= PRESENT VALUE
of cfgCO
2
SensorOffset
<=1000
Tips of configuring
cfgCO
2
SensorOffset:
1. There must be an interval
of 3 minutes between the
two times calibrations of
CO
2
written into TR50, and
less than this interval
writing operation will cause
failure.
2. TR50 can only accept the
CO
2
sensor offset value
which meets requirement
that CO
2
sensor reading +
offset value > 400 ppm
SS_MV_OutOfRange_CO
2
3 R/W Multi
State
Value
1 1: Normal
2: Over high limit
3: Over highhigh limit
CfgAlarmCO
2
LimitEnable 23 R/W Multi
State
Value
4 1: CO
2
High Limit And
High High Limit Disable
2: CO
2
High Limit Enable
3: CO
2
High High Limit
Enable
4: CO
2
High Limit And
High High Limit Enable