TR50 - User Guide 21
4.4.5.5 PM2.5 Configuration Points
Point Name
BACnet
Instance
Read/
Write
Type
Default
Value
Range
CfgAlarmPM2.5HighLimit 151 R/W Analog
Value
35(ug/m
3
)
0<= PRESENT VALUE of
cfgAlarmPM2.5HighLimit
<= PRESENT VALUE of
cfgAlarmPM2.5HighHigh
Limit
cfgAlarmPM2.5HighHigh
Limit
152 R/W Analog
Value
55(ug/m
3
)
PRESENT VALUE of
cfgAlarmPM2.5 HighLimit
<= PRESENT VALUE of
cfgAlarmPM2.5
HighHighLimit <=5000
CfgAlarmPM2.5Deadband 153 R/W Analog
Value
5 0 <= PRESENT VALUE of
cfgAlarmPM2.5Deadband
CfgAlarmPM2.5TimeDelay 154 R/W Analog
Value
60(s) 0 <= PRESENT VALUE of
cfgAlarmPM2.5TimeDelay
CfgPM2.5SensorOffset 284 R/W Analog
Value
0
SS_MV_OutOfRange_PM2.5 4 R/W Multi
State
Value
1 1: Normal
2: Over high limit
3: Over highhigh limit
CfgAlarmPM2.5LimitEnable 24 R/W Multi
State
Value
4 1:PM2.5 High Limit And
High High Limit Disable
2:PM2.5 High Limit Enable
3:PM2.5 High High Limit
Enable
4:PM2.5 High Limit And
High High Limit Enable
CfgPM1.0SensorOffset 287 R/W Analog
Value
0
CfgPM10SensorOffset 288 R/W Analog
Value
0