22 TR50 - User Guide
4.4.5.6 TVOC Configuration Points
Point Name
BACnet
Instance
Read/
Write
Type
Default
Value
Range
CfgAlarmTVOCHighLimit 201 R/W Analog
Value
250(ppb)
500(ug/m
3
)
8(ppb)
<= PRESENT VALUE
of
cfgAlarmTVOCHighLi
mit
<= PRESENT VALUE
of
cfgAlarmTVOCHighHi
ghLimit
16(ug/m3)
<= PRESENT VALUE
of
cfgAlarmTVOCHighLi
mit
<= PRESENT VALUE
of
cfgAlarmTVOCHighHi
ghLimit
CfgAlarmTVOCHighHighLimit 202 R/W Analog
Value
350(ppb)
700(ug/m
3
)
PRESENT VALUE of
cfgAlarmTVOCHigh
Limit
<= PRESENT
VALUE of
cfgAlarmTVOCHigh
HighLimit
<=2820(ppb)
PRESENT VALUE of
cfgAlarmTVOCHigh
Limit
<= PRESENT
VALUE of
cfgAlarmTVOCHigh
HighLimit
<=5640(ug/m3)
CfgAlarmTVOCDeadband 203 R/W Analog
Value
20(ppb)
40(ug/m
3
)
0(ppb) <= PRESENT
VALUE of
cfgAlarmTVOCDead
band
0(ug/m3) <=
PRESENT VALUE of
cfgAlarmTVOCDead
band
CfgAlarmTVOCTimeDelay 204 R/W Analog
Value
60(s)
0 <= PRESENT
VALUE of
cfgAlarmTVOCTime
Delay
CfgTVOCSensorOffset 285 R/W Analog
Value
0
SS_MV_OutOfRange_TVOC 5 R/W Multi State
Value
1 1: Normal
2: Over high limit
3: Over highhigh
limit