TR50 - User Guide 23
4.4.5.7 Configuration Points
CfgAlarmTVOCLimitEnable 25 R/W Multi State
Value
4 1:TVOC High Limit
And High High
Limit Disable
2:TVOC High Limit
Enable
3:TVOC High High
Limit Enable
4:TVOC High Limit
And High High
Limit Enable
cfgDisplayUnitTVOC 102 R/W Multi State
Value
1 1: Parts Per Billion
2: Micrograms Per
Cubic Meter
Point Name
BACnet
Instance
Read/
Write
Type
Default
Value
Range
Point Name
BACnet
Instance
Read/
Write
Type
Default
Value
Range
SS_MV_AQI_level 6 R Multi State Value 1 1: Good
2: Moderate
3: Unhealthy
cfgAQIUnhealthyScore 251 R/W Analog Value 40 0
<= PRESENT VALUE of
cfgAQIUnhealthyScore
<= PRESENT VALUE of
cfgAQIModerateScore
cfgAQIModerateScore 252 R/W Analog Value 80 PRESENT VALUE of
cfgAQIUnhealthyScore
<= PRESENT VALUE of
cfgAQIModerateScore
<=100
CfgAlarmAQIDeadband 253 R/W Analog Value 2 0 <= PRESENT VALUE of
cfgAlarmAQIDeadband
CfgAlarmAQITimeDelay 254 R/W Analog Value 60(s) 0 <= PRESENT VALUE of
cfgAlarmAQITimeDelay
CfgAlarmAQILimitEnable 26 R/W Multi State Value 4
1: AQI Moderate Limit
And Unhealthy Limit
Disable
2: AQI Moderate Limit
Enable
3: AQI Unhealthy Limit
Enable
4: AQI Moderate And
Unhealthy Limit Enable