24 TR50 - User Guide
4.4.5.8 User Interface Configuration
Point Name
BACnet
Instance
Read/
Write
Type
Default
Value
Range
cfgLedRingBrightness 301 R/W Analog Value 50 40-100
CfgLedRingDimBrightness 302 R/W Analog Value 10 10-40
CfgLcdBrightness 321 R/W Analog Value 80 40-100
CfgLcdDimBrightness 322 R/W Analog Value 40 10-40
CfgLcdAutoCycleTime 341 R/W Analog Value 5(s) 3-10(s)
cfgLedRingLcdTimeoutTime 361 R/W Analog Value 0(s) 0(s), 10-30(s)
cfgLedRingLcdDimTime 362 R/W Analog Value 10(s) 3-10(s)
CfgIsParaDisplayed 381 R/W Analog Value TR50-5D: 63
TR50-3D: 15
For TR50-5D,
cfgIsDisplayed_AQI -
Bit 0
cfgIsDisplayed_Temp -
Bit 1
cfgIsDisplayed_Humi -
Bit 2
cfgIsDisplayed_CO2 -
Bit 3
cfgIsDisplayed_PM2.5 -
Bit 4
cfgIsDisplayed_TVOC -
Bit 5
For TR50-3D,
cfgIsDisplayed_AQI -
Bit 0
cfgIsDisplayed_Temp -
Bit 1
cfgIsDisplayed_Humi -
Bit 2
cfgIsDisplayed_CO2 -
Bit 3
cfgLedRingLcdEnable 21 R/W Binary Value 1 0: Off
1: On
CfgLedRingColorOption 61 R/W Multi State
Value
1 1: Color mode
2: Neutral mode