TR50 - User Guide 25
4.4.5.9 BACnet Configuration Points
CfgLcdParameterSwitch 81 R/W Multi State 
Value
1 For TR50-5D, 
1: Auto cycling (default)
2: Manual + AQI (as the 
static page)
3: Manual + Tempera-
ture (as the static page)
4: Manual + Humidity 
(as the static page)
5: Manual + CO2 (as the 
static page)
6: Manual + PM2.5 (as 
the static page)
7: Manual + TVOC (as 
the static page)
8: Manual + no static 
page
For TR50-3D, 
1: Auto cycling (default)
2: Manual + AQI (as the 
static page)
3: Manual + Tempera-
ture (as the static page)
4: Manual + Humidity 
(as the static page)
5: Manual + CO2 (as the 
static page)
6: Manual + no static 
page
CfgAlarmIndicatorEnable 41 R/W Multi State 
Value
4
1:Disable
2:cfgOutOfRangeAlarm
IndicatorEnable
3:cfgSensorFailureAlarm
IndicatorEnable
4:cfgOutOfRangeAlarm
IndicatorEnable && 
cfgSensorFailureAlarm
IndicatorEnable
Point Name
BACnet 
Instance
Read/
Write
Type
Default 
Value
Range
Point Name BACnet Instance Read/Write Type
Default 
Value
Range
MstpHeaderCrcErrCount 500 R Analog Value -
MstpDataCrcErrCount 501 R Analog Value -
CfgIsMstpBadCrcClear 41 R/W Binary Value 1 0: Uncleared
1: Cleared