EasyManua.ls Logo

Honeywell TR50 - Page 38

Honeywell TR50
86 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
TR50 - User Guide 33
Setup 2030 R/W NV
cfgAlarmTemp
LowLimit
3N/
3D/
5N/5D
signed/
int16
16
32
o
F<= cfgAlarmTempLow
Limit <=
cfgAlarmTempHighLimit
0°C <=
cfgAlarmTempLowLimit <=
cfgAlarmTem-pHighLimit
65
o
F
18 °C
Setup 2031 R/W NV
cfgAlarmHumiLow
Limit
3N/
3D/
5N/5D
int16 16 0 <= cfgAlarmHumiLow-
Limit <= cfgAlarmHumi-
HighLimit
10%
Setup 2032 R/W NV
cfgAlarm
CO
2
HighLimit
3N/
3D/
5N/5D
int16 16 0 <= cfgAlarmCO2High-
Limit <= cfgAlarm-
CO2HighHighLimit
1000ppm
Setup 2033 R/W NV
cfgAlarmPM2.5
HighLimit
5N/5D int16 16 0 <= cfgAlarmPM2.5High-
Limit <= cfgAlarm-
PM2.5HighHighLimit
35ug/m
3
Setup 2034 R/W NV
cfgAlarmT
VOC
HighLimit
5N/5D int16 16 8 ppb <= cfgAlarmT-
VOCHighLimit <=
cfgAlarmTVOCHighHigh-
Limit
16 ug/m3<= cfgAlarmT-
VOCHighLimit <=
cfgAlarmTVOCHighHigh-
Limit
250 ppb
500 ug/
m
3
Setup 2035 R/W NV
cfgAQIModerate
Score
3N/
3D/
5N/5D
int16 16 cfgAQIUnhealthy-
Score<=cfgAQIModerate-
Score<=100
80
Setup 2050 R/W NV
cfgAlarmTemp
HighLimit
3N/
3D/
5N/5D
signed/
int16
16 cfgAlarmTempLowLimit <=
cfgAlarmTempHighLimit
<= 122°F
cfgAlarmTempLowLimit <=
cfgAlarmTempHighLimit
<= 50°C
86
o
F
30 °C
Setup 2051 R/W NV
cfgAlarmHumi
HighLimit
3N/
3D/
5N/5D
int16 16 cfgAlarmHumiLowLimit <=
cfgAlarmHumiHighLimit
<= 100
80%
Setup 2052 R/W NV
cfgAlarm
CO
2
HighHigh
Limit
3N/
3D/
5N/5D
int16 16 cfgAlarmCO2HighLimit <=
cfgAlarmCO2HighHigh-
Limit <= 9999
1400ppm
Setup 2053 R/W NV cfgAlarmPM2.5
HighHighLimit
5N/5D int16 16 cfgAlarmPM2.5HighLimit
<= cfgAlarmPM2.5High-
HighLimit <= 5000
55ug/m
3
Setup 2054 R/W NV
cfgAlarmT
VOC
HighHigh
Limit
5N/5D int16 16 cfgAlarmTVOCHighLimit
<= cfgAlarmTVOCHigh-
HighLimit<=2820 ppb
cfgAlarmTVOCHighLimit
<= cfgAlarmTVOCHigh-
HighLimit<=5640ug/m3
350 ppb
700 ug/
m
3
Setup 2055 R/W NV
cfgAQIUnhealthy
Score
3N/
3D/
5N/5D
int16 16 0<= cfgAQIUnhealthyScore
<= cfgAQIModerateScore
<= 100
40
Setup 2070 R/W NV
cfgAlarmTemp
Deadband
3N/
3D/
5N/5D
int16 16 0 <= cfgAlarmTempDead-
band
1(
o
F)
1(°C)
Setup 2071 R/W NV
cfgAlarmHumi
Deadband
3N/
3D/
5N/5D
int16 16 0 <= cfgAlarmHumiDead-
band
2
Setup/
Runtime
Addr Dir
Non-
Volatile
Name SKU Type/Unit
Bits
Num
Range Default

Table of Contents

Related product manuals