34 TR50 - User Guide
Setup 2072 R/W NV
cfgAlarm
CO
2
Deadband
3N/
3D/
5N/5D
int16 16
0 <=
cfgAlarmCO2Deadband
100
Setup 2073 R/W NV
cfgAlarmPM2.5
Deadband
5N/5D int16 16
0 <=
cfgAlarmPM2.5Deadband
5
Setup 2074 R/W NV
cfgAlarmTVOC
Deadband
5N/5D int16 16
0 <=
cfgAlarmTVOCDeadband
20(ppb)
40(ug/m3)
Setup 2075 R/W NV
cfgAlarmAQIDead
band
3N/
3D/
5N/5D
int16 16
0 <=
cfgAlarmAQIDeadband
2
Setup 2090 R/W NV
cfgAlarmTempTime
Delay
3N/
3D/
5N/5D
int16 16
0 <=
cfgAlarmTempTimeDelay
60(s)
Setup 2091 R/W NV
cfgAlarmHumiTime
Delay
3N/
3D/
5N/5D
int16 16
0 <=
cfgAlarmHumiTimeDelay
60(s)
Setup 2092 R/W NV
cfgAlarmCO
2
TimeDelay
3N/
3D/
5N/5D
int16 16
0 <= cfgAlarmCO2Time
Delay
60(s)
Setup 2093 R/W NV
cfgAlarmPM2.5
TimeDelay
5N/5D int16 16
0 <=
cfgAlarmPM2.5TimeDelay
60(s)
Setup 2094 R/W NV
cfgAlarmTVOC
TimeDelay
5N/5D int16 16
0 <=
cfgAlarmTVOCTimeDelay
60(s)
Setup 2095 R/W NV
cfgAlarmAQITime
Delay
3N/
3D/
5N/5D
int16 16 0 <= cfgAlarmAQITime
Delay
60(s)
Setup 2110 R/W NV
Cfg_OORSensor
FailAlarmIndicator
En
3D/5D enum/
int16
16
1:Disable
2:cfgOutOfRangeAlarmInd
icatorEnable
3:cfgSensorFailureAlarmIn
dicatorEnable
4:cfgOutOfRangeAlarmInd
icatorEnable &&
cfgSensorFailureAlarmIndi
cat orEnable
4
Setup 2130 R/W NV
cfgIsParaDisplayed
3D/5D int16 16 For TR50-5D,
cfgIsDisplayed_AQI - Bit 0
cfgIsDisplayed_Temp -
Bit 1
cfgIsDisplayed_Humi -
Bit 2
cfgIsDisplayed_CO2 - Bit 3
cfgIsDisplayed_PM2.5 -
Bit 4
cfgIsDisplayed_TVOC -
Bit 5
For TR50-3D,
cfgIsDisplayed_AQI - Bit 0
cfgIsDisplayed_Temp -
Bit 1
cfgIsDisplayed_Humi -
Bit 2
cfgIsDisplayed_CO2 - Bit 3
15/63
Setup/
Runtime
Addr Dir
Non-
Volatile
Name SKU Type/Unit
Bits
Num
Range Default