TR50 - User Guide 35
Setup 2150 R/W NV
cfgTempAlarm
LimitEnable
3N/
3D/
5N/5D
enum/
int16
16 1:Temp Low Limit And
High Limit Disable
2:Temp Low Limit Enable
3:Temp High Limit Enable
4:Temp Low Limit And
High Limit Enable
4
Setup 2151 R/W NV
cfgHumiAlarm
LimitEnable
3N/
3D/
5N/5D
enum/
int16
16 1:Humidity Low Limit And
High Limit Disable
2:Humidity Low Limit
Enable
3:Humidity High Limit
Enable
4:Humidity Low Limit And
High Limit Enable
4
Setup 2152 R/W NV
cfgCO
2
AlarmLimit
Enable
3N/
3D/
5N/5D
enum/
int16
16 1:CO2 High Limit And High
High Limit
Disable
2:CO2 High Limit Enable
3:CO2 High High Limit
Enable
4:CO2 High Limit And High
High Limit
Enable
4
Setup 2153 R/W NV
cfgPM25Alarm
LimitEnable
5N/5D enum/
int16
16 1:PM2.5 High Limit And
High High Limit
Disable
2:PM2.5 High Limit Enable
3:PM2.5 High High Limit
Enable
4:PM2.5 High Limit And
High High Limit
Enable
4
Setup 2154 R/W NV
cfgTVOCAlarm
LimitEnable
5N/5D enum/
int16
16 1:TVOC High Limit And
High High Limit Disable
2:TVOC High Limit Enable
3:TVOC High High Limit
Enable
4:TVOC High Limit And
High High Limit Enable
4
Setup 2155 R/W NV
cfgAQIAlarmLimit
Enable
3N/
3D/
5N/5D
enum/
int16
16 1: AQI Moderate Limit And
Unhealthy Limit Disable
2: AQI Moderate Limit
Enable
3: AQI Unhealthy Limit
Enable
4: AQI Moderate And
Unhealthy Limit Enable
4
Setup 3000 R/W NV
cfgLedRingColor
Option
3N/
3D/
5N/5D
int16 16 1: Color mode
2: Neutral mode
1
Setup 3001 R/W NV
cfgLedRing
Brightness
3N/
3D/
5N/5D
int16 16 40-100 50
Setup 3002 R/W NV
cfgLedRingDim
Brightness
3D/5D int16 16 10-40 10
Setup 3020 R/W NV
cfgLcdAutoCycle
Time
3D/5D int16 16 3-10(s) 5(s)
Setup 3021 R/W NV cfgLcdBrightness 3D/5D int16 16 40-100 80
Setup/
Runtime
Addr Dir
Non-
Volatile
Name SKU Type/Unit
Bits
Num
Range Default