36 TR50 - User Guide
Setup 3022 R/W NV
cfgLcdParameter
Switch
3D/5D enum/
int16
16 For TR50-5D,
1: Auto cycling (default)
2: Manual + AQI (as the
static page)
3: Manual + Temperature
(as the static page)
4: Manual + Humidity (as
the static page)
5: Manual + CO2 (as the
static page)
6: Manual + PM2.5 (as the
static page)
7: Manual + TVOC (as the
static page)
8: Manual + no static page
For TR50-3D,
1: Auto cycling (default)
2: Manual + AQI (as the
static page)
3: Manual + Temperature
(as the static page)
4: Manual + Humidity (as
the static page)
5: Manual + CO2 (as the
static page)
6: Manual + no static page
1
Setup 3023 R/W NV
cfgLcdDimBright
ness
3D/5D int16 16 10-40 40
Setup 3030 R/W NV
cfgLedRingLcd
DimTime
3D/5D int16 16 3-10(s) 10s
Setup 3031 R/W NV
cfgLedRingLcd
TimeoutTime
3D/5D int16 16 0(s), 10-30(s) 0(s)
Setup 4000 R/W NV
cfgTemperature
Unit
3N/
3D/
5N/5D
bit/bool
ean
1 -Fahrenheit: 0
-Celsius: 1
Fahren
heit
Setup 4001 R/W NV
cfgDisplayUnit
Temp
3D/5D
bit/bool
ean
1 -Fahrenheit: 0
-Celsius: 1
Fahren
heit
Setup 4004 R/W NV cfgTVOCUnit 5N/5D
bit/bool
ean
1 -ppb: 0
-ug/m
3
: 1
ppb
Setup 4005 R/W NV
cfgDisplayUnit
TVOC
5D
bit/bool
ean
1 -ppb: 0
-ug/m
3
: 1
ppb
Setup 4020 R/W NV
cfgLedRingLcd
Enable
3N/
3D/
5N/5D
bit/bool
ean
1 ON or OFF ON/1
Setup 5000 R/W NV
cfgModbusAuto
BaudrateEnable
3N/
3D/
5N/5D
bool 1 TRUE or FALSE TRUE
Setup 5001 R/W V
cfgModbusFrame
CntClear
3N/
3D/
5N/5D
bool 1 TRUE or FALSE TRUE
Setup 5040 R/W NV
cfgLocalDetection
Enable
3N/
3D/
5N/5D
bool 1 TRUE or FALSE TRUE
Setup/
Runtime
Addr Dir
Non-
Volatile
Name SKU Type/Unit
Bits
Num
Range Default