48 TR50 - User Guide
4.6.1.2 Sensor Alarm
There are two scenarios to do alarming in the controller.
1. TR50 can detect the alarm locally and the alarm value can be given to the
controller.
2. User can disable the local alarm in the TR50 and then write the alarm value from
the controller to the TR50.
The second scenario will be useful when there is more than one device in a single
zone.
Follow the below steps to configure the Alarm locally and give the value to the
controller:
Step 1. Double click on the TR50 Sensor Parameter.
Step 2. On the Property sheet navigate to Sylk Config Data and expand
tR5xConfig.
The first property under tR5xConfig is the alarm limits. By default, both low limit
and high limits are enabled, and user can configure these limits as a fixed value or
dynamic linkable value.