Table 6.3 %SR Registers Master %SR Table
Register
Default I/O
Name
Description
Min-Max
Values
Program
(Read/Write)
Display
(Read/Write)
%SR206-
208
Reserved
%SR209.3
WebMI Server Status. Bit 3 is ON if
server running.
Read Only
Read Only
%SR209.4
WebMI User Logged in Status. Bit 4 is
ON if 1 or more users logged in.
Read Only
Read Only
%SR209.8-
209.16
Number of Users. Shows in upper byte
in decimal format.
Read Only
Read Only
%SR210
Time Zone: set in minutes + / - UTC.
(Ex: EST is -4 hours = -240 minutes)
Read/Write
Read/Write
%SR211
Daylight Saving: YES = 1
Daylight Saving: NO = 0
(If daylight saving is enabled, one hour
will be added to the local time).
Read/Write
Read/Write
%SR212
UTC Seconds
Read Only
Read Only
%SR213
UTC Minutes
Read Only
Read Only
%SR214
UTC Hours
Read Only
Read Only
%SR215
UTC Date
Read Only
Read Only
%SR216
UTC Month
Read Only
Read Only
%SR217
UTC Year
Read Only
Read Only
%SR218
Number of Webpages, license detail
(XLE/XLT, X2, X4, & X7 use %SR101 &
%SR108-112 for WebMI License Details.)
Read Only
Read Only
%SR219
Number of Data Points, license detail.
(XLE/XLT, X2, X4, & X7 use %SR101 &
%SR108-112 for WebMI License Details)
Read Only
Read Only
%SR220-222
Expiration Date of WebMI License,
license detail.
(XLE/XLT, X2, X4, & X7 use %SR101 &
%SR108-112 for WebMI License Details)
Read Only
Read Only