FusionModule5000 Smart Modular Data Center
Maintenance Guide (ECC800)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
2.5 Routine Maintenance for the Intelligent Battery
Monitoring System
Only trained personnel are allowed to maintain the intelligent battery monitoring system of
the data center. For safety requirements, see safety precautions in iBAT 2.0-CIM01C2 User
Manual.
Table 2-13 Routine maintenance items
No battery
management alarm
is generated.
Find the cause of an
alarm based on the
alarm information.
After you wipe the
battery surface using
a piece of white
paper, the paper
does not turn black.
Remove dust from
the battery surface.
Ambient
temperature
detection
The ambient
temperature should
be lower than 45°C.
Find the cause of an
abnormal
temperature.
Battery management
parameter setting
Check that the
battery management
parameters are set
based on site
requirements.
Set parameters
correctly.
The BIM is
attached firmly.
All BIM cables
are securely
connected.
No BIM cable
deteriorates and
the insulation
layer does not
crack.
Secure the BIM
again.
Verify that all
BIM cables are
securely
connected.
Replace the
faulty cable.
The CIM is
attached firmly.
The cable to the
PoE port is
connected
securely.
If a cable is
connected to the
COM port, check
that the cable
connection is
Secure the CIM
again.
Reconnect the
cable to the PoE
port.
Reconnect the
cable to the
COM port.
Reconnect the
cable to the BCB