FusionModule5000 Smart Modular Data Center
Maintenance Guide (ECC800)
3 Alarm Reference
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
55
3.1.2 Integrated UPS Alarm Reference
Alar
m
ID
(Ala
rm
ID-
Cau
se
ID)
Alarm
Name
Sever
ity
System Action
Cause
Solution
0001
-1
Mains
voltage
abnorm
al
Minor
If there is no
battery, the system
transfers to bypass
mode or shuts
down based on
logic.
Cable
connections
are incorrect.
The mains is
abnormal.
The power
module is
faulty.
1. Check whether
cables to mains
are
disconnected,
loose, or
incorrectly
connected.
2. If cable
connections are
correct, measure
the mains
voltage with a
multimeter. If
the mains
voltage exceeds
280 V, the mains
input is
abnormal; if the
mains voltage is
less than 272 V,
the sampling
circuit of the
power module is
abnormal.
Replace the
faulty module.
0001
-2
Cable
connections
are incorrect.
The mains is
abnormal.
The mains
input fuse for
the power
module is
blown.
1. Check whether
cables to mains
are
disconnected,
loose, or
incorrectly
connected.
2. If cable
connections are
correct, measure
the mains
voltage with a
multimeter. If
the mains

Table of Contents

Other manuals for Huawei FusionModule5000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei FusionModule5000 and is the answer not in the manual?

Huawei FusionModule5000 Specifications

General IconGeneral
BrandHuawei
ModelFusionModule5000
CategoryWireless Router
LanguageEnglish

Related product manuals