2.6.13 Routine Maintenance for Water Sensors
Table 2-27 Routine maintenance for water sensors
Check the
availability of
the water
sensor.
Drip water on
the water
detection cable
using a cup, and
view active
alarms on the
WebUI.
A water alarm
is generated on
the WebUI.
If no water
alarm is
displayed on
the WebUI,
check whether
the water sensor
cable is loose or
disconnected. If
the cable is
properly
connected,
replace the
water sensor.
2.6.14 Routine Maintenance for Temperature Sensors
Table 2-28 Routine maintenance for temperature sensors
Check the
availability of
the temperature
sensor.
Hold the
temperature
sensor probe in
your palm, and
check the
temperature
displayed for
the
corresponding
rack
environment
Temperature
displayed for
the
corresponding
rack
environment
unit goes up on
the WebUI.
If the
temperature
does not go up,
check whether
the temperature
sensor cable is
loose or
disconnected. If
so, reconnect
the cable. If not,
replace the