Step 8 Place the removed fan module in an ESD bag.
----End
Installing a Fan Module
Step 1 Wear an ESD wrist strap. For details, see 5.2 ESD Protection.
You can skip steps Step 2 to Step 4 and Step 9 to Step 11 when you can open the chassis
cover without removing the server. The scenarios include but are not limited to: (1) the
server is installed on adjustable guide rails and (2) the server is not installed in a cabinet.
Step 2 Power o the server. For details, see 5.4.2 Powering O the Server.
Step 3 Remove the power cables. For details, see 5.7 PSU.
Step 4 Remove the server. For details, see 5.4.4 Removing the Server and Guide Rails.
Step 5 Remove the chassis cover. For details, see 5.8 Chassis Cover.
Step 6 Take a spare fan module out of its ESD bag.
Step 7 Insert the fan module along the guide rails into the slot until you hear a click.
Check that the fan cable connector is securely inserted into the mainboard
connector. See Figure 5-40.
Fan modules on the same server must have the same Part No.
TaiShan 200 Server
Maintenance and Service Guide (Model 2280) 5 Removal and Installation
Issue 04 (2020-01-16) Copyright © Huawei Technologies Co., Ltd. 108