Figure E-3 Active Alarms screen
Step 2 Cancel the battery maintenance notication function.
NO TE
If you do not want the battery maintenance notication 0036-01 to appear again, perform
the following steps:
1. On the Main Menu screen, select Settings and press
. The Settings login
screen is displayed. The preset password is 000001. After you enter the correct
password and press
, the Settings screen is displayed.
2. UPS2000-G-15KRTL-01/UPS2000-G-20KRTL-01: Choose Battery Parameters
and Shallow Discharge, and then change the value of Scheduled test from
Enable to Disable (congurable when the UPS works in any mode).
Figure E-4 Shallow Discharge screen (UPS2000-G-15KRTL-01/UPS2000-
G-20KRTL-01)
UPS2000-G-6KRTS/UPS2000-G-10KRTS/UPS2000-G-15KRTL/UPS2000-
G-20KRTL: Choose Battery Parameters and Shallow Discharge, and then
change the value of Test notication from Enabled to Disabled
(congurable when the UPS works in any mode).
Figure E-5 Shallow Discharge screen (UPS2000-G-6KRTS/UPS2000-
G-10KRTS/UPS2000-G-15KRTL/UPS2000-G-20KRTL)
----End
UPS2000-G-(6 kVA–20 kVA)
User Manual (Lead-Acid Battery)
E Alarm Handing of Battery Maintenance
Notication
Issue 23 (2024-03-15) Copyright © Huawei Digital Power Technologies Co., Ltd. 168