3.7 ECO Specications
Table 3-13 ECO specications
Item 6 kVA 10 kVA 15 kVA 20 kVA
ECO voltage
tolerance
Default value: ±10% (congurable on the LCD)
The range is ±5% to 10%
ECO frequency
tolerance
Default value: ±2 Hz (congurable on the LCD)
The range is ±0.5 Hz to ±3 Hz
3.8 System Electrical Specications
Table 3-14 Parallel system specications
Item 6 kVA 10 kVA 15 kVA 20 kVA
Number of UPSs
in parallel (dual
live wires)
1+1
Number of UPSs
in parallel (other
mode except dual
live wires)
≤ 4
Power distribution
system
TN, TN-C, TN-C-S, TT
Pollution degree PD2
NO TE
The UPS2000-G-15 kVA/20 kVA (single-phase input single-phase output) supports 3+1
parallel systems at most, instead of 4+0 parallel systems.
3.9 Safety Regulations and EMC
Table 3-15 Safety compliance
Safety
Certication Standard
CE EN IEC 62040-1
CB IEC 62040-1
UPS2000-G-(6 kVA–20 kVA)
User Manual (Lead-Acid Battery) 3 Technical Specications
Issue 23 (2024-03-15) Copyright © Huawei Digital Power Technologies Co., Ltd. 47