Item Description Default
Value
Value Range
BPS
backfe
ed
Set the output dry contact associated
with bypass backfeed. When a bypass
backfeed alarm is generated, this dry
contact is enabled.
Dry
contact
5
Dry contacts 1–
6
Faulty
UPS
Set the output dry contact associated
with UPS faults. When a critical
alarm is generated, this dry contact is
enabled.
Dry
contact
6
Dry contacts 1–
6
5.6.3.3 System Parameters Screen
● Parallel screen
Figure 5-27 Parallel screen
Table 5-18 Parallel settings
Item
Description Default
Value
Value Range
Single/Parallel Species whether the UPS
works in single mode or
parallel mode. This
parameter is congurable
only after the inverter is
shut down.
Single Single, Parallel
Redundant UPSs Set the number of redundant
UPSs. This parameter is
congurable only after the
inverter is shut down.
0 0–3
● Output screen
Figure 5-28 Output screen
UPS2000-G-(6 kVA–20 kVA)
User Manual (Lead-Acid Battery) 5 Control Panel
Issue 23 (2024-03-15) Copyright © Huawei Digital Power Technologies Co., Ltd. 86