F Battery Shallow Discharge Test
Context
A shallow discharge test method that tests the battery loop reliability and short-
time backup capacity after batteries are charged for a long time (60 days by
default, 30 days to 90 days congurable).
NO TICE
Before a shallow discharge test, ensure that the load rate is 0%–100% and the
load uctuation does not exceed 10%.
Procedure
Step 1 Check the battery status for test start conditions.
1. On the Main Menu screen, choose Status and press
. On the Status
screen, locate Battery Status.
Figure F-1 Battery Status screen
UPS2000-G-(6 kVA–20 kVA)
User Manual (Lead-Acid Battery) F Battery Shallow Discharge Test
Issue 23 (2024-03-15) Copyright © Huawei Digital Power Technologies Co., Ltd. 169