Item 6 kVA 10 kVA 15 kVA 20 kVA
Bypass overload
capability
When the UPS works continuously at a load rate of less
than 125%, the input switch may trip in advance.
When the load rate is within 125%–150%, the UPS
disconnects the output after 1 minute, and the input
switch may trip in advance.
When the load rate is greater than or equal to 150%,
the UPS disconnects the output after 100 ms, and the
input switch may trip in advance.
Input mode One power source One power source
Two power sources
NO TE
The upper and lower thresholds are congurable on the LCD.
3.5 Output Electrical Specications
Table 3-7 Output electrical specications
Item
6 kVA 10 kVA 15 kVA 20 kVA
Rated capacity 6 kVA 10 kVA 15 kVA 20 kVA
Output power
factor (PF)
0.9
Output short-
circuit current
- - Ipeak: 5 kA; Irms: 3.5 kA
(typical power supply
duration: 4 ms)
Rated output
voltage
208 V AC, 220 V AC, 230 V
AC, or 240 V AC (single-
phase output; select a
voltage system by setting a
voltage level on the LCD.)
208 V AC, 220 V AC, 230
V AC, or 240 V AC (single-
phase output; select a
voltage system by setting
a voltage level on the
LCD.)
380 V AC, 400 V AC, or
415 V AC (three-phase
output; select a voltage
system by setting a
voltage level on the LCD.)
Output voltage
tolerance
±1%
UPS2000-G-(6 kVA–20 kVA)
User Manual (Lead-Acid Battery) 3 Technical Specications
Issue 23 (2024-03-15) Copyright © Huawei Digital Power Technologies Co., Ltd. 38