Item 6 kVA 10 kVA 15 kVA 20 kVA
Bypass overload
capability
● When the UPS works continuously at a load rate of less
than 125%, the input switch may trip in advance.
● When the load rate is within 125%–150%, the UPS
disconnects the output after 1 minute, and the input
switch may trip in advance.
● When the load rate is greater than or equal to 150%,
the UPS disconnects the output after 100 ms, and the
input switch may trip in advance.
Input mode One power source ● One power source
● Two power sources
The upper and lower thresholds are congurable on the LCD.
3.5 Output Electrical Specications
Table 3-7 Output electrical specications
Item
6 kVA 10 kVA 15 kVA 20 kVA
Rated capacity 6 kVA 10 kVA 15 kVA 20 kVA
Output power
factor (PF)
0.9
Output short-
circuit current
- - Ipeak: 5 kA; Irms: 3.5 kA
(typical power supply
duration: 4 ms)
Rated output
voltage
208 V AC, 220 V AC, 230 V
AC, or 240 V AC (single-
phase output; select a
voltage system by setting a
voltage level on the LCD.)
● 208 V AC, 220 V AC, 230
V AC, or 240 V AC (single-
phase output; select a
voltage system by setting
a voltage level on the
LCD.)
● 380 V AC, 400 V AC, or
415 V AC (three-phase
output; select a voltage
system by setting a
voltage level on the LCD.)
Output voltage
tolerance
±1%
UPS2000-G-(6 kVA–20 kVA)
User Manual (Lead-Acid Battery) 3 Technical Specications
Issue 23 (2024-03-15) Copyright © Huawei Digital Power Technologies Co., Ltd. 38