EasyManua.ls Logo

Huawei UPS2000-G - Setting Battery Parameters

Huawei UPS2000-G
186 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Item Description Defau
lt
Value
Value
Range
Auto
check bus
capa.
Species whether to automatically check
the bus capacitance upon power-on and
generate capacitance failure warnings. If
the value is set to Enabled, the UPS
startup time takes additional 30 seconds
to 180 seconds. This parameter is
congurable only after the inverter is
shut down.
Note: This parameter is congurable only
for the 15 kVA/20 kVA UPS.
Enabl
ed
Disabled,
Enabled
Auto start Species whether to automatically start
normal mode after the UPS connects to
the mains. This parameter is
congurable only after the inverter is
shut down.
Disabl
ed
Disabled,
Enabled
No
battery
alarm
If this parameter is set to Disable, the No
battery alarm is not reported. This
parameter automatically changes to
Enable after batteries are connected. This
parameter is congurable only when
batteries are not connected.
NOTE
If batteries are connected and you try to set
this parameter, the system displays a message
indicating that batteries are connected and this
parameter cannot be set.
Enabl
ed
Disabled,
Enabled
EPO
enable
Species whether to enable EPO. EPO is
performed only when this parameter is set
to Enable and the EPO switch is triggered.
This parameter is congurable only for
the UPS2000-G-15KRTL-01/UPS2000-
G-20KRTL-01.
Disabl
ed
Disabled,
Enabled
5.6.3.4 Setting Battery Parameters
CA UTION
The congured number of batteries on the LCD must match the actual number.
When the actual number changes, update the congured number. If the
congured number is less than the actual number, the battery lifespan is
shortened. If the congured number is greater than the actual number, battery
leakage may cause a re.
UPS2000-G-(6 kVA–20 kVA)
User Manual (Lead-Acid Battery) 5 Control Panel
Issue 23 (2024-03-15) Copyright © Huawei Digital Power Technologies Co., Ltd. 95