Table 5-24 Other settings
Item Description Defau
lt
Value
Value
Range
Recovery
delay time
Delay time that the UPS takes in
transferring from battery mode to normal
mode when the mains recovers This
parameter is congurable only after the
inverter is shut down.
NOTE
If Recovery delay time(s) is set to 0S, the
actual recovery delay time is 1 second.
5s 0–900s
Maximum
bypass
transfer
times
Maximum number of bypass transfers
within 30 minutes When the number of
bypass transfers exceeds this value, the
UPS keeps running in bypass mode (in
ECO mode, the UPS keeps running in
inverter mode). This parameter is
congurable only after the inverter is
shut down.
NOTICE
Do not set the UPS to ECO mode when the UPS
connects to an isolated transformer.
3 1–3
Output
transform
er
If an output transformer is connected, set
the parameter to Enabled; otherwise, set it
to Disabled. This parameter is
congurable only after the inverter is
shut down.
NOTE
When connecting an isolation transformer to
the system output, connect the UPS output
load to the pL terminal and disable the power
segment function.
Disabl
ed
Disabled,
Enabled
Generator
mode
If the mains input voltage quality is good,
Weak adaptability mode is
recommended. If the mains input voltage
is of average quality (for example, a high-
performance generator or a common
power grid is connected), Balance mode is
recommended. If the mains input voltage
quality is poor (for example, a common
generator is connected), Strong
adaptability mode is recommended. This
parameter is congurable only after the
inverter is shut down.
Balan
ce
mode
Weak
adaptabi
lity
mode,
Balance
mode,
Strong
adaptabi
lity
mode
UPS2000-G-(6 kVA–20 kVA)
User Manual (Lead-Acid Battery) 5 Control Panel
Issue 23 (2024-03-15) Copyright © Huawei Digital Power Technologies Co., Ltd. 94