Item 15 kVA 20 kVA
Input voltage ● 80–280 V AC, single-phase
(When the voltage is 80–
176 V AC, the load power
is linearly derated to
40%–100%.)
● 138–485 V AC, three-
phase (When the voltage
is 138–305 V AC, the load
power is linearly derated
to 40%–100%.)
● 80–280 V AC, single-
phase (When the voltage
is 80–176 V AC, the load
power is linearly derated
to 40%–100%.)
● 138–485 V AC, three-
phase (When the voltage
is 138–305 V AC, the load
power is linearly derated
to 40%–100%.)
Input power
factor (100%
resistive load)
> 0.99
No-load loss < 200 W
Double-power
input
Enabled
Startup voltage 120–280 V AC
Generator input
capacity
Minimum 1.5 times the UPS rated capacity
Overvoltage
category
OVC Ⅱ
3.4 Bypass Input Electrical Specications
Table 3-6 Bypass input electrical specications
Item
6 kVA 10 kVA 15 kVA 20 kVA
Bypass voltage ● Upper threshold: 10%, 15%, 20%, 25%, or 30% at 208 V
AC
● Upper threshold: 10%, 15%, 20%, or 25% at 220 V AC
● Upper threshold: 10%, 15%, or 20% at 230 V AC
● Upper threshold: 10% or 15% at 240 V AC
● Lower threshold: 10%, 20%, 30%, 40%, 50%, or 60%
Bypass frequency
tolerance
Maximum ±6 Hz (congurable on the LCD)
UPS2000-G-(6 kVA–20 kVA)
User Manual (Lead-Acid Battery) 3 Technical Specications