Huawei UPS2000-G - Battery Electrical Specifications

Huawei UPS2000-G
186 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Item 6 kVA 10 kVA 15 kVA 20 kVA
Total harmonic
distortion of
output voltage
(THDv)
< 4% (non-linear load)
< 2% (resistive load)
Crest factor A maximum of 3:1
Inverter overload
capability
105% ≤ load < 125%: transfer to bypass mode after 5
minutes
125% ≤ load < 150%: transfer to bypass mode after 1
minute
Load ≥ 150%: transfer to bypass mode after 100
milliseconds
The UPS stops supplying power if the bypass is
abnormal.
Dynamic voltage
tolerance
±5%
Output voltage
unbalance
- ±1% (balanced load)
±3% (unbalanced load)
Average
frequency
tracking rate
0.5–2 Hz/s (single UPS) or 0.5–1 Hz/s (parallel system)
Power segment
(supported only
for a single UPS)
If overloaded, the UPS disconnects the loads on pL and
checks whether it is still overloaded.
In battery mode, when the battery voltage is less than
the preset value, the UPS disconnects the loads on pL.
In battery mode, when the battery discharge time
exceeds the preset value, the UPS disconnects the loads
on pL.
NO TE
In converter mode, the output load is derated to 60% of the rated capacity.
3.6 Battery Electrical Specications
Table 3-8 Battery electrical specications
Item
6 kVA 10 kVA 15 kVA 20 kVA
Rated battery
voltage
240 V DC ± 240 V DC
UPS2000-G-(6 kVA–20 kVA)
User Manual (Lead-Acid Battery) 3 Technical Specications
Issue 23 (2024-03-15) Copyright © Huawei Digital Power Technologies Co., Ltd. 39