Item 6 kVA 10 kVA 15 kVA 20 kVA
Number of
batteries
16–20, each 12 V
If the smaller value
between the numbers of
batteries,
N
, is less than
20, the battery power is
derated to
N
/20.
16–20 batteries in each of
positive and negative strings
(The total number of batteries
is 32–40.)
The rated number of batteries
in each string is 20. If the
number of batteries is less
than 20, the power is derated
to
N
/20 (
N
is the smaller
value between the numbers of
batteries in positive and
negative strings).
Battery string
sharing in a
parallel system
Not
supported
Not
supported
Supported Supported
Battery leakage
current
≤ 500 µA
Depth of
discharge (DOD)
protection
The discharge time is longer than 16 hours (can be set to
0–24 hours, 16 hours by default. If the time is set to 0
hours, battery discharge protection is not implemented).
The single-battery voltage drops below 10.8 V in normal
mode.
Standard-UPS
battery type
12 V DC VRLA battery
Standard-UPS
battery capacity
7 Ah 9 Ah - -
Backup time > 4 minutes, full rated load For details about the backup
time curve of the battery pack, see Figure 3-1, Figure 3-2,
Figure 3-3, and Figure 3-4.
Parallel
connection
Batter strings can be connected in parallel. If the user
prepares batteries, the maximum number of battery strings
in parallel is specied by the battery manufacturer. A
maximum of four battery strings are recommended.
UPS2000-G-(6 kVA–20 kVA)
User Manual (Lead-Acid Battery) 3 Technical Specications
Issue 23 (2024-03-15) Copyright © Huawei Digital Power Technologies Co., Ltd. 40

Table of Contents