Table 3-12 Backup time parameters for the ESS-240V12-9AhBPVBA01/
ESS-240V12-9AhBPVBA04 battery pack (20 kVA, calculated based on 94% battery
eciency)
Load (%) Load (W) Two
Battery
Packs
(min)
Four
Battery
Packs
(min)
Six Battery
Packs
(min)
Eight
Battery
Packs
(min)
100% 18000 4 12 23 32
80% 14400 7 17 29 44
50% 9000 12 32 53 70
30% 5400 26 57 88 125
Figure 3-4 Backup time curve for the ESS-240V12-9AhBPVBA01/
ESS-240V12-9AhBPVBA04 battery pack (20 kVA, calculated based on 94% battery
eciency)
UPS2000-G-(6 kVA–20 kVA)
User Manual (Lead-Acid Battery) 3 Technical Specications
Issue 23 (2024-03-15) Copyright © Huawei Digital Power Technologies Co., Ltd. 46