Table 3-11 Backup time parameters for the ESS-240V12-9AhBPVBA01/
ESS-240V12-9AhBPVBA04 battery pack (15 kVA, calculated based on 94% battery
eciency)
Load (%) Load (W) Two
Battery
Packs
(min)
Four
Battery
Packs
(min)
Six Battery
Packs
(min)
Eight
Battery
Packs
(min)
100% 13500 7 19 32 48
80% 10800 9 26 44 57
50% 6750 18 48 70 96
30% 4050 35 79 125 171
Figure 3-3 Backup time curve for the ESS-240V12-9AhBPVBA01/
ESS-240V12-9AhBPVBA04 battery pack (15 kVA, calculated based on 94% battery
eciency)
UPS2000-G-(6 kVA–20 kVA)
User Manual (Lead-Acid Battery) 3 Technical Specications