Model Wiring
Termina
l
Numb
er of
Phases
Rated
Voltage
External
Circuit
Breaker
Cable
Cross-
Sectional
Area
Terminal
Type
Torque
for
Tighteni
ng Bolts
15 kVA
(dual-live-
wire input
dual-live-
wire output)
Dual-
live-wire
input
2 208 V
AC/220 V AC
100 A/2 P
(character
istic D)
25 mm
2
25 mm
2
M6 OT
terminal
4.8 N·m
Battery - ± 240 V DC 63 A/4P
16 mm
2
16 mm
2
M6 90°
OT
terminal
4.8 N·m
Dual-
live-wire
Output
2 208 V
AC/220 V AC
100 A/2 P
(character
istic D)
25 mm
2
25 mm
2
M6 OT
terminal
4.8 N·m
15 kVA
(single-
phase input
single-phase
output)
Input 1 220 V
AC/230 V
AC/240 V AC
100 A/2 P
(character
istic D)
25 mm
2
25 mm
2
M6 OT
terminal
4.8 N·m
Battery - ± 240 V DC 63 A/4P
16 mm
2
16 mm
2
M6 90°
OT
terminal
4.8 N·m
Output 1 220 V
AC/230 V
AC/240 V AC
100 A/2 P
(character
istic D)
25 mm
2
25 mm
2
M6 OT
terminal
4.8 N·m
15 kVA
(three-phase
input single-
phase
output)
Bypass
input
1 220 V
AC/230 V
AC/240 V AC
100 A/2 P
(character
istic D)
25 mm
2
25 mm
2
M6 OT
terminal
4.8 N·m
Mains
input
3 380 V
AC/400 V
AC/415 V AC
50 A/4 P
(character
istic D)
10 mm
2
10 mm
2
M6 OT
terminal
2.8 N·m
Battery - ± 240 V DC 63 A/4P
16 mm
2
16 mm
2
M6 90°
OT
terminal
4.8 N·m
Output 1 220 V
AC/230 V
AC/240 V AC
100 A/2 P
(character
istic D)
25 mm
2
25 mm
2
M6 OT
terminal
4.8 N·m
15 kVA
(three-phase
input three-
phase
output)
Bypass
input
3 380 V
AC/400 V
AC/415 V AC
50 A/4 P
(character
istic D)
10 mm
2
10 mm
2
M6 OT
terminal
2.8 N·m
Mains
input
3
UPS2000-G-(6 kVA–20 kVA)
User Manual (Lead-Acid Battery) 4 Installation
Issue 23 (2024-03-15) Copyright © Huawei Digital Power Technologies Co., Ltd. 57

Table of Contents

Related product manuals