Model Single-Phase/Three-Phase Dual–Live Wire
Rated Voltage
and Rated
Current
Recommended
Backfeed
Protection
Device Model
(Schneider
Contactor)
Rated
Voltage and
Rated
Current
Recommen
ded
Backfeed
Protection
Device
Model (ABB
Contactor)
UPS2000-
G-15KRTL
(three-
phase
input)
220 V AC/230 V
AC/240 V AC, 32
A
Three-phase
input: contactor
LC1-DT60A
- -
UPS2000-
G-20KRTL
(three-
phase
input)
220 V AC/230 V
AC/240 V AC, 40
A
- -
UPS2000-
G-15KRTL
(single-
phase
input)
UPS2000-
G-20KRTL
(single-
phase
input)
220 V AC/230 V
AC/240 V AC,
125 A
Single-phase
input: LC1-D80
contactor
208 V
AC/220 V
AC, 125 A
Contactor
AF110-30-11
*70
UPS2000-
G-15KRTL
-01
(three-
phase
input)
220 V AC/230 V
AC/240 V AC, 32
A
Three-phase
input: contactor
LC1-DT60A
- -
UPS2000-
G-20KRTL
-01
(three-
phase
input)
220 V AC/230 V
AC/240 V AC, 40
A
- -
UPS2000-G-(6 kVA–20 kVA)
User Manual (Lead-Acid Battery) 4 Installation
Issue 23 (2024-03-15) Copyright © Huawei Digital Power Technologies Co., Ltd. 62