Table 5-21 ECO settings
Item Description Defau
lt
Value
Value Range
Max.
voltage
Upper threshold for the ECO
voltage. In ECO mode, when the
dierence between the bypass
voltage and the rated voltage is
greater than this value, the system
determines that the ECO voltage is
abnormal and transfers to normal
mode. This parameter is
congurable only after the
inverter is shut down.
10% 5%, 6%, 7%,
8%, 9%, 10%
Min.
voltage
Lower threshold for the ECO
voltage. In ECO mode, when the
dierence between the bypass
voltage and the rated voltage is
lower than this value, the system
determines that the ECO voltage is
abnormal and transfers to normal
mode. This parameter is
congurable only after the
inverter is shut down.
10% 5%, 6%, 7%,
8%, 9%, 10%
Frequenc
y range
ECO frequency range. In ECO mode,
when the dierence between the
bypass frequency and the rated
frequency is beyond this range, the
system determines that the ECO
frequency is abnormal and transfers
to normal mode.
The Frequency range parameter is
associated with the bypass
frequency range and must be less
than the current bypass frequency
range. This parameter is
congurable only after the
inverter is shut down.
±2 Hz ±0.5 Hz, ±1 Hz,
±2 Hz,±3 Hz
Single
UPS ECO
Determine whether to support ECO
mode on a single UPS (ECO mode is
not supported in a parallel system).
Disabl
ed
Disabled,
Enabled
● Power Segment screen
UPS2000-G-(6 kVA–20 kVA)
User Manual (Lead-Acid Battery) 5 Control Panel