Water is leaking
from upper part of
steam cylinder.
Hose clamps on the steam or condensate
hose do not close tightly.
Tighten hose clamps.
XX
The heater element or thermo sensor has not
been properly installed.
Install heater element and thermo
sensor as specified in the unit
manual.
Steam hose adapter has not been correctly
installed or o-ring has not been changed.
Replace o-ring and correctly install
steam hose adapter.
If condensate is not into the steam cylinder,
the condensate connection must have a
condensate plug.
Install condensate plug.
XX
No steam produc-
tion, even though
the steam genera-
tor has been acti-
vated. The display
is active.
Performing a signal
test and a steam
requirement test
may give additional
information about
the cause of the
malfunction. See
Section System
Test.
If the temperature exceeds the set desired
value, no steam demand is present.
The unit has been switched off remotely.
(Terminals 1 and 2 in the steam generator are
not bridged.)
Poor air circulation, steam bath temperature
has remained above the programmed set
value for a long period of time.
Check desired and actual
temperature values.
Switch on the unit using the remote
switch, or install a jumper between
terminals 1 and 2.
Install a fan.
X
No steam produc-
tion. Current is sup-
plied to the
electrodes, but no
water is being fed.
Water supply is not open or solenoid valve
has not been electrically triggered.
Open water supply.
Also see Fault Filling.