Page 79
Water is leaking
from upper part of
steam cylinder.
• Hose clamps on the steam or condensate
hose do not close tightly.
• Tighten hose clamps.
XX
• The heater element or thermo sensor has not
been properly installed.
• Install heater element and thermo
sensor as specified in the unit
manual.
• Steam hose adapter has not been correctly
installed or o-ring has not been changed.
• Replace o-ring and correctly install
steam hose adapter.
• If condensate is not into the steam cylinder,
the condensate connection must have a
condensate plug.
• Install condensate plug.
XX
No steam produc-
tion, even though
the steam genera-
tor has been acti-
vated. The display
is active.
Performing a signal
test and a steam
requirement test
may give additional
information about
the cause of the
malfunction. See
Section System
Test.
•
•
•
If the temperature exceeds the set desired
value, no steam demand is present.
The unit has been switched off remotely.
(Terminals 1 and 2 in the steam generator are
not bridged.)
Poor air circulation, steam bath temperature
has remained above the programmed set
value for a long period of time.
•
•
•
Check desired and actual
temperature values.
Switch on the unit using the remote
switch, or install a jumper between
terminals 1 and 2.
Install a fan.
X
No steam produc-
tion. Current is sup-
plied to the
electrodes, but no
water is being fed.
• Water supply is not open or solenoid valve
has not been electrically triggered.
•
•
Open water supply.
Also see Fault Filling.
HL ***
Hy,C***
Possible Condi-
tions
Probable Cause for fault situation Resolution