Distribution Series 3 Dual Bus
855-314-002_Rev2.0_Instruction Manual
Page 24 of 46
Ignore Circuit Breaker Status: Select to disable alarms from this
output. Will prevent false alarms on an unused channel. The default
setting is Disabled.
Enable Power Cycling: Select this box to enable output power cycling
for the selected output. Enabled outputs will automatically be re-enabled
after the "Sequence/Cycle Delay" time whenever the output is disabled
using the "Output Off" button on the "Status & Control" page, or when
the Network Watchdog is triggered. This feature is useful for remotely
resetting power to a router or other hardware required for the network
connectivity of the unit. The default setting is Disabled.
NOTE: The "Sequence/Cycle Delay" time must be set on the "Device Setup"
page with duration long enough for the connected network
hardware to fully reset for this function to be effective. Multiple
outputs that are disabled using Power Cycling will be re-enabled in
sequence from output #1 to output #6.
Output Load-Shedding
Load shedding will disable specified outputs when the bus voltage reaches
a preset threshold for at least 30 seconds. This will save battery capacity for
mission-critical load devices by turning off non-critical load devices. Loads
will be reconnected if Load-Shedding Auto Recovery is enabled, and the
bus voltage exceeds the Auto Recovery Threshold for 60 seconds
Enable Load-Shedding: Set this box to enable load-shedding on this
output. The default setting is Disabled.
Load-Shedding Threshold: Set the voltage (1–60 VDC) at which the
selected output will be disabled. The default setting is 10.50 VDC.
Load-Shedding Auto Recovery: Set this box to allow the output to be
automatically reconnected when the bus voltage is above the "Recovery
Threshold". The default setting is Disabled.
Auto Recovery Threshold: Set the voltage (1.5–60.5 VDC) at which
the selected output will automatically be reconnected. This value must

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ICT Distribution 3 Series and is the answer not in the manual?

ICT Distribution 3 Series Specifications

General IconGeneral
BrandICT
ModelDistribution 3 Series
CategoryPower distribution unit
LanguageEnglish

Related product manuals