MAGIS COMBO 9 V2
46
MAGIS COMBO 9 V2 Water ow temperature °C
15 18 25
Air temperature °C
d.b.
Max. output
(kW)
Max. absorbed
(kW)
Max. output
(kW)
Max. absorbed
(kW)
Max. output
(kW)
Max. absorbed
(kW)
10 9.02 1.54 9.63 1.57 10.59 1.60
20 8.68 1.75 9.27 1.78 10.19 1.82
30 8.33 1.96 8.89 1.99 9.78 2.03
35 8.15 2.07 8.70 2.11 9.57 2.15
46 7.77 2.29 8.29 2.33 9.12 2.38
MAGIS COMBO 9 V2 Water ow temperature °C
7 10 13
Air temperature °C
d.b.
Max. output
(kW)
Max. absorbed
(kW)
Max. output
(kW)
Max. absorbed
(kW)
Max. output
(kW)
Max. absorbed
(kW)
10 7.20 1.45 7.80 1.48 8.41 1.51
20 6.92 1.65 7.51 1.68 8.09 1.72
30 6.64 1.84 7.21 1.88 7.77 1.92
35 6.50 1.95 7.05 1.99 7.60 2.03
46 6.19 2.15 6.72 2.20 7.24 2.24
30.1 “POWER” AND ABSORPTION” IN COOLING MODE