MAGIS COMBO 9 V2
45
- Correction factor stated DC = 0.9
- TOL = -25 °C
MAGIS COMBO 9 V2 Water ow temperature °C
55 60 65
Air temperature °C
d.b. (w.b.)
Max. output
(kW)
Max. absorbed
(kW)
Max. output
(kW)
Max. absorbed
(kW)
Max. output
(kW)
Max. absorbed
(kW)
-20 (-21)
-15 (-16)
-10 (-11) 6.63 3.90
-7 (-8) 6.96 4.12
-2 (-3) 6.48 3.85 6.14 4.28
2 (1) 6.16 3.15 5.84 3.50
7 (6) 8.00 2.73 7.72 2.96 7.44 3.20
10 (9) 8.50 2.95 8.07 3.05 7.65 3.14
15 (14) 9.76 3.02 9.27 3.11 8.78 3.21
20 (19) 11.02 3.09 10.47 3.18 9.91 3.28
MAGIS COMBO 9 V2 Water ow temperature °C
40 45 50
Air temperature °C
d.b. (w.b.)
Max. output
(kW)
Max. absorbed
(kW)
Max. output
(kW)
Max. absorbed
(kW)
Max. output
(kW)
Max. absorbed
(kW)
-20 (-21) 6.14 2.93 5.90 3.23
-15 (-16) 7.07 3.08 6.87 3.26 6.66 3.43
-10 (-11) 7.60 3.21 7.37 3.39 7.15 3.56
-7 (-8) 7.73 3.27 7.56 3.65 7.26 3.88
-2 (-3) 7.50 2.83 7.20 3.08 6.84 3.47
2 (1) 7.27 2.39 6.84 2.52 6.50 2.84
7 (6) 8.80 2.10 8.60 2.33 8.30 2.53
10 (9) 9.64 2.12 9.44 2.36 8.97 2.66
15 (14) 11.03 2.13 10.84 2.42 10.30 2.72
20 (19) 12.42 2.18 12.24 2.47 11.63 2.78
30 “POWER” AND “ABSORPTION” IN CENTRAL HEATING MODE
MAGIS COMBO 9 V2 MAGIS COMBO 9 PLUS V2
MAGIS COMBO 9 V2 Water ow temperature °C
25 30 35
Air temperature °C
d.b. (w.b.)
Max. output
(kW)
Max. absorbed
(kW)
Max. output
(kW)
Max. absorbed
(kW)
Max. output
(kW)
Max. absorbed
(kW)
-20 (-21) 6.90 2.28 6.71 2.44 6.39 2.74
-15 (-16) 7.86 2.41 7.64 2.58 7.28 2.90
-10 (-11) 8.47 2.52 8.23 2.70 7.84 3.04
-7 (-8) 8.53 2.41 8.30 2.58 7.90 2.90
-2 (-3) 8.42 2.14 8.19 2.30 7.80 2.58
2 (1) 8.32 1.88 8.09 2.01 7.70 2.26
7 (6) 9.72 1.55 9.45 1.66 9.00 1.87
10 (9) 10.62 1.57 10.32 1.68 9.83 1.89
15 (14) 12.11 1.59 11.78 1.70 11.22 1.91
20 (19) 13.61 1.61 13.23 1.73 12.60 1.94