79
INSTALLER
USERMAINTENANCE TECHNICIAN
TECHNICAL DATA
Id
Parameter
Parameter Description Range Default
Value
value
t9 Display
Establishes what the indicator 11 displays (Fig. 38).
"Summer" mode:
0: the indicator is always o
1: active pump displays the ow temperature, pump o the
indicator is o
"Winter" mode:
0: always displays the value set on the C.H. selector
1: active pump displays the ow temperature, pump o
always displays the value set on the C.H. selector
0 - 1 1
t10
Flow o
temperature
increase
Increases the ow o temperature at ignition only in the rst
60 seconds. Aer the ame is detected, the temperature is
increased by t10
0 - 15 0
t11 Not used on this boiler model 0 - 1 0
Id
Parameter
Parameter Description Range Default
Value
value
A0
Hydraulic
model
Denes the type of hydraulics in the boiler 0 0
A1 - Not used on this boiler model - -
A2
Circulating
pump model
Denes the type of circulator in the boiler 0 ÷ 1 0
A3
Maximum
pump speed
Sets the maximum pump operating speed 1 ÷ 9 9
A4
Minimum
pump speed
Sets the minimum pump operating speed 1 ÷ A3 7
A5
Circulating
pump mode
Sets the pump operating mode
- DELTA T = 0: proportional head (Parag. 1.29 - 1.30)
- DELTA T = 5 - 25 K: ∆T constant (Parag. 1.29 - 1.30)
0 ÷ 25 15
Id
Parameter
Parameter Description Range Default
Value
value
F0 Flue length Denes the length of the ue (Par. 3.12) 0 - 2 0
F1 - Not used on this boiler model - -
In the event of an alteration, anomaly “E72” appears and fast calibration is required.