71
INSTALLER
USERMAINTENANCE TECHNICIAN
TECHNICAL DATA
3.10 CO2 REGULATION
During the complete calibration (Par. 3.9) it is possible to modify the CO
2
values.
In order to have an exact value of
CO
2 in the ue gas, the technician must insert the sampling probe into the well to the bottom
In case of calibration for propane air, select the analyser in LPG gas mode.
Check that theCO
2
value is the one indicated in the table (Par. 4.2), (considering a maximum tolerance of ± 0.2%), otherwise change the
value as described below:
During calibration, when the “
” symbol starts ashing (indicating the correct acquisition of the parameters) it is possible to alter the
CO
2
value by pressing the buttons 5 or 6 ( ).
In this phase, the previously activated icons together with the “external connected devices presence icon” (
) will ash on the display
and the operating temperature alternated with combustion setting is displayed.
48
To increase the combustion setting, press the button 5 (
), to decrease it, press
the button 6 (
). As the combustion setting increases, the CO
2
value decreases
and vice-versa.
Once the parameter has been altered wait for the value to be saved (displayed via the “
” symbol ashing).
To conrm the value set, press “
” followed by “ ” again in order to go to the next calibration.