70
INSTALLER
USERMAINTENANCE TECHNICIAN
TECHNICAL DATA
Ignition intermediate heat output
Once the nominal heat output calibration is conrmed, the appliance is calibrated with the intermediate heat output (or ignition heat
output).
At this stage the display features ashing icons: “
” and “ ” and the operating temperature alternated with the current operating heat
output (e.g.: 41%) is displayed; once the parameters are detected and stabilised, the “ ” symbol will start ashing, meaning that the
nominal heat output settings have been set.
46
Only aer the “
” symbol ashes is it possible to change the CO
2
value
(Par. 3.10) or switch to the next heat output parameter by pressing the “
button.
Minimum heat output
Aer having calibrated the boiler with the intermediate heat output, it is calibrated with the minimum heat output.
At this stage the display features ashing icons: “
” and “ ” and the operating temperature alternated with the current operating heat
output (0%) is displayed; once the parameters are detected and stabilised, the “
” symbol will start ashing, meaning that the minimal
heat output settings have been set.
47
Only aer the “
” symbol ashes is it possible to change the CO
2
value
(Par. 3.10) or switch to the calibration self-check phase by pressing the “
button.
Calibration self-check
Once calibration operations are complete, the boiler runs a self-check for about one minute. During this check, the boiler can run at dif-
ferent powers and it is not possible to apply modications to the operating parameters or to delete the operation in progress. Moreover, it
is important not to cut the boiler's power.