F1-06 to F1-10 to the default values of the standard motor parameters (Y series
asynchronous motor).
If it is impossible to perform motor auto-tuning in the field, manually input the values of
these parameters according to the motor of similar type.
Function Code Parameter Name Setting Range Default
0 No auto-tuning
1
Static auto-tuning (certain motor
parameters obtained)
2
Complete auto-tuning (complete
motor parameters obtained)
F1-11
Motor auto-tuning
mode
3
Static auto-tuning (complete
motor parameters obtained)
0
Before motor auto-tuning, set motor ratings (F1-00 to F1-05) properly.
z 0: No auto-tuning
Auto-tuning is prohibited.
z 1: Static auto-tuning
It is applicable to the applications where the motor must be connected with the load.
To perform static auto-tuning, set F1-11 to 1 and press the key RUN.
z 2: Complete auto-tuning
To ensure the AC drive’s dynamic control performance, perform complete auto-tuning,
which requires the motor to be disconnected from the load.
The AC drive performs static auto-tuning first. After the static auto-tuning is complete,
the AC drive accelerates to 80% of the rated motor frequency within the system
default acceleration time (20s if the AC drive power 55 kW, 50s if the AC drive
power > 55 kW). Then the AC drive keeps running at 80% of the rated motor
frequency for a certain period and then decelerates to 0 within the same deceleration
time.
To perform complete auto-tuning, set F1-11 to 2 and press the key RUN.
z 3: Static auto-tuning
To facilitate the user to obtain more accurate motor parameters in the applications
where the motor cannot be disconnected from the load, the CS500 has the function of
obtaining complete motor parameters from static auto-tuning. The function requires
longer auto-tuning time.
To perform complete auto-tuning, set F1-11 to 3 and press the key RUN.
After you set F1-11 correctly and press the key ENTER, "TUNE" is displayed and blinks.
Press the RUN key to start auto-tuning, and the displayed TUNE stops blinking. During
auto-tuning, press the key STOP to stop auto-tuning. After the auto-tuning ends, F1-16
resumes to 0 automatically, and the display returns to the stop status interface.
Motor auto-tuning can be performed only in operation panel control mode.
Group F2: Vector Control Parameters
Group F2 is valid for vector control (F0-01=0 or 1), and invalid for V/F control (F0-01=2).
Function Code Parameter Name Setting Range Default
F2-00 Speed loop proportional gain 1 0–100 60
F2-01 Speed loop integral time 1 0.01–10.00s 0.50s
F2-02 Switchover frequency 1 0.00 to F2-05 5.00 Hz
efesotomas