MD500 User Manual 6. Parameter Table
- 87 -
Function Code Parameter Name Setting Range Default Property
F2-02 Switchover frequency 1 0.00 to F2-05 5.00 Hz
ƿ
F2-03 Speed loop proportional gain 2 1 to 100 20
ƿ
F2-04 Speed loop integral time 2 0.01s to 10.00s 1.00s
ƿ
F2-05 Switchover frequency 2 F2-02 to max. frequency 10.00 Hz
ƿ
F2-06 Vector control slip gain 50% to 200% 100%
ƿ
F2-07 6SHHGORRSÀOWHUWLPHFRQVWDQW 0.000s to 0.100s 0.000s
ƿ
) Torque upper limit source
in speed control mode
0 to 7 0
ƿ
F2-10 Digital setting of torque upper
limit in speed control mode
0.0% to 200.0% 150.0%
ƿ
F2-11 Torque limit source in speed
control (regenerative)
0 to 7 0
ƿ
F2-12 Digital setting of torque limit in
speed control regenerative)
0.0% to 200.0% 150.0%
ƿ
F2-13 ([FLWDWLRQDGMXVWPHQW
proportional gain
0 to 60000 2000
ƿ
F2-14 ([FLWDWLRQDGMXVWPHQW
integral gain
0 to 60000 1300
ƿ
F2-15 7RUTXHDGMXVWPHQW
proportional gain
0 to 60000 2000
ƿ
F2-16 7RUTXHDGMXVWPHQWLQWHJUDOJDLQ 0 to 60000 1300
ƿ
F2-17 Speed loop integral
separation selection
0: Disabled
1: Enabled
ƿ
F2-20 0D[RXWSXWYROWDJHFRHIÀFLHQW 100% to 110%
105%
ƾ
F2-21 0D[WRUTXHFRHIÀFLHQWRI
ÀHOGZHDNHQLQJDUHD
50% to 200% 100%
ƿ
*URXS)9)&RQWURO3DUDPHWHUV
F3-00 9)FXUYHVHWWLQJ 0 to 11 0
ƾ
F3-01 Torque boost 0.0% to 30% Model
dependent
ƿ
F3-02 Cut-off frequency of torque boost 0.00 Hz to max. frequency 50.00 Hz
ƾ
F3-03 0XOWLSRLQW9)IUHTXHQF\) 0.00 Hz to F3-05 0.00 Hz
ƾ
F3-04 0XOWLSRLQW9)YROWDJH9 0.0% to 100.0% 0.0%
ƾ
F3-05 0XOWLSRLQW9)IUHTXHQF\) F3-03 to F3-07 0.00 Hz
ƾ
F3-06 0XOWLSRLQW9)YROWDJH9 0.0% to 100.0% 0.0%
ƾ
F3-07 0XOWLSRLQW9)IUHTXHQF\) F3-05 to rated motor frequency (F1-04) 0.00 Hz
ƾ
F3-08 0XOWLSRLQW9)YROWDJH9 0.0% to 100.0% 0.0%
ƾ
) 9)VOLSFRPSHQVDWLRQJDLQ 0.0% to 200.0% 0.0%
ƾ
F3-10 9)RYHUH[FLWDWLRQJDLQ 0 to 200 64
ƿ
F3-11 9)RVFLOODWLRQVXSSUHVVLRQJDLQ 0 to 100 40
ƿ
F3-13 9ROWDJHVRXUFHIRU9)VHSDUDWLRQ 0 to 8 0
ƿ