6. Parameter Table MD500 User Manual
Function Code Parameter Name Setting Range Default Property
F8-37 Output overcurrent
detection delay
0.00s to 600.00s 0.00s
ƿ
F8-38 Detection of current 1 0.0% to 300.0% (rated motor current) 100.0%
ƿ
) Detection width of current 1 0.0% to 300.0% (rated motor current) 0.0%
ƿ
F8-40 Detection of current 2 0.0% to 300.0% (rated motor current) 100.0%
ƿ
F8-41 Detection width of current 2 0.0% to 300.0% (rated motor current) 0.0%
ƿ
F8-42 Timing function 0, 1 0
ƾ
F8-43 Timing running time
setting channel
0 to 3 0
ƾ
F8-44 Timing running time 0.0 to 6500.0 min 0.0 min
ƾ
F8-45 AI1 input voltage lower limit 0.00 V to F8-46 3.10 V
ƿ
F8-46 AI1 input voltage upper limit F8-45 to 10.00 V 6.80 V
ƿ
F8-47 Module temperature threshold 0°C to 100°C 75°C
ƿ
F8-48 Cooling fan working mode 0, 1 0
ƿ
) Wakeup frequency Hibernating frequency (F8-51)
to max. frequency (F0-10)
0.00 Hz
ƿ
F8-50 Wakeup delay time 0.0s to 6500.0s 0.0s
ƿ
F8-51 Hibernating frequency +]WRZDNHXSIUHTXHQF\) 0.00 Hz
ƿ
F8-52 Hibernating delay time 0.0s to 6500.0s 0.0s
ƿ
F8-53 Current running time 0.0 to 6500.0 min 0.0 min
ƿ
*URXS))DXOWDQG3URWHFWLRQ
) Motor overload
protection selection
0, 1 1
ƿ
) Motor overload protection gain 0.20 to 10.00 1.00
ƿ
) Motor overload pending
FRHIÀFLHQW
50% to 100% 80%
ƿ
) Overvoltage stall gain 0 (no overvoltage stall) to 100 0
ƿ
) Overvoltage stall
protective voltage
9WR) 9
ƿ
) Overcurrent stall gain 0 to 100 20
ƿ
) Overcurrent stall protective level 100% to 200% 150%
ƾ
) Detection of short-circuit to
ground upon power-on
0, 1 1
ƿ
) Braking unit action voltage 700 to 800 V 780 V
ƾ
) Auto reset times 0 to 20 0
ƿ
) Selection of DO action
during auto reset
0, 1 0
ƿ
) Delay of auto reset 0.1s to 100.0s 1.0s
ƿ
) Selection of power input phase
ORVVFRQWDFWRUFORVHSURWHFWLRQ
00 to 11 11
ƿ
) Power output phase
loss protection
0, 1 1
ƿ
) 1st fault type 0 to 55 - ƕ
) 2nd fault type 0 to 55 - ƕ
) 3rd (latest) fault type 0 to 55 - ƕ
) Frequency upon 3rd fault - - ƕ
) Current upon 3rd fault - - ƕ
) Bus voltage upon 3rd fault - - ƕ
) DI state upon 3rd fault - - ƕ
) Digital output terminal
state upon 3rd fault
--ƕ