MD500 User Manual 6. Parameter Table
Function Code Parameter Name Setting Range Default Property
) AC drive state upon 3rd fault - - ƕ
) Current power-on time
upon 3rd fault
--ƕ
) Current running time
upon 3rd fault
--ƕ
) Frequency upon 2nd fault - - ƕ
) Current upon 2nd fault - - ƕ
) Bus voltage upon 2nd fault - - ƕ
) DI state upon 2nd fault - - ƕ
) Digital output terminal
state upon 2nd fault
--ƕ
) AC drive state upon 2nd fault - - ƕ
) Current power-on time
upon 2nd fault
--ƕ
) Current running time
upon 2nd fault
--ƕ
) Frequency upon 1st fault - - ƕ
) Current upon 1st fault - - ƕ
) Bus voltage upon 1st fault - - ƕ
) DI state upon 1st fault - - ƕ
) Digital output terminal
state upon 1st fault
--ƕ
) AC drive state upon 1st fault - - ƕ
) Current power-on time
upon 1st fault
--ƕ
) Current running time
upon 1st fault
--ƕ
) Fault protection action selection 1 00000 to 22222 00000
ƿ
) Fault protection action selection 2 00000 to 11111 00000
ƿ
) Fault protection action selection 3 00000 to 22222 00000
ƿ
) Fault protection action selection 4 00000 to 22222 00000
ƿ
) Frequency selection for
continuing to run upon fault
0 to 4 0
ƿ
) Backup frequency
upon abnormality
0.0% to 100.0% (max. frequency) 100.0%
ƿ
) Type of motor temperature sensor 0: No temperature sensor
1: PT100
2: PT1000
0
ƿ
) Motor overheat
protection threshold
0°C to 200°C 110°C
ƿ
) Motor overheat pending threshold 0°C to 200°C &
ƿ
) Power dip ride-through
function selection
0 to 2 0
ƾ
) Voltage level of power dip ride-
through function disabled
80% to 100% 85%
ƾ
) Judging time of bus voltage
recovering from power dip
0.0s to 100.0s 0.5s
ƾ
) Voltage level of power dip ride-
through function enabled
60% to 100% 80%
ƾ
) Selection of load lost protection 0: Disabled
1: Enabled
0
ƿ