Electrical Installation
‑145‑
Table 8–8 Cable selection (single‑phase 200 V to 240 V) (with UL certification)
Stru
ctur
e
Drive Model
Rated
Input
Current
(A)
R/S/T, U/V/W
Grounding Cable
Screw
Recommend
ed Input
Cable
(mm
2
)
<1>
Recom
mended
Output
Cable
(mm
2
)
<1>
Recommend
ed Cable Lug
Recommend
ed Cable
(mm
2
)
<1>
Recommend
ed Cable Lug
T2 MD520‑
2S0.4B(S)
5.4 18 18 TLK0.75‐4 18 TLK0.75‐4 M4
MD520‑
2S0.7B(S)
8.2 18 18 TLK1.25‐4 18 TLK1.25‐4
MD520‑
2S1.5B(S)
14 16 16 TLK1.25‐4 16 TLK1.25‐4
MD520‑
2S2.2B(S)
23 12 12 TLK3.5‐4 12 TLK3.5‐4
Note
<1>: Chinese standards applicable; 3 x 10: one three‑conductor cable; 2 x (3 x 95): two
three‑conductor cables; <2>: American standards applicable; 5: 5AWG; 1/0: 0AWG; 2/0:
00AWG; 3/0: 000AWG; 4/0: 0000AWG; 2 x 250: two 250 kcmil cables
Recommended cable lug
The following table describes recommended lugs, namely, the TNR, GTNR, and BC
series lugs of Suzhou Yuanli. The lugs with UL certifications are TLK and SQNBS series
lugs of KST.