Electrical Installation
154
Table 8–12 Requirement for output reactor based on cable length and motor types
AC Drive Rated
Power (kW)
Maximum Cable
Length of the
Common
Asynchronous Motor
(Without Output
Reactor)
Output Reactor
Required
(Motor Complying
with IEC 60034‑25 IVIC
B)
Output Reactor
Required
(Common
Asynchronous
Induction Motor)
0.43.7 50 m
Not required Required
5.5 70 m
Not required Required
7.5 100 m
Not required Required
11 110 m
Not required Required
15 125 m
Not required Required
18.5 135 m
Not required Required
22 150 m
Not required Required
30
150 m
Not required Required
Recommended cable lugs
The following table describes the appearances of the GTNR and BC series cable lugs
of Suzhou Yuanli.
Table 8–13 Appearance of cable lugs
Series
Appearance
GTNR series
TNR series
BC series