EasyManua.ls Logo

Inovance MD520 Series - Page 164

Inovance MD520 Series
198 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Electrical Installation
‑163‑
Figure 8‑40 Parallel connection of DIs of multiple AC drives in the sink mode
Source wiring mode
Figure 8‑41 Source wiring mode
To use the internal 24 V power supply of the drive, remove the jumper between
the +24V and OP terminals, connect the OP terminal to the COM terminal, and
connect the +24V terminal of the drive to the common terminal of the external
controller, as shown in the following figure.
To use an external power supply, remove the jumper between the +24V and the
OP terminals, connect the OP terminal of the drive to the 0V terminal of the
external power supply, and connect the 24 V positive electrode of the external
power supply to the corresponding DI through the external controller contact.

Table of Contents

Other manuals for Inovance MD520 Series

Related product manuals