PROFIBUS DP Communication
150
Figure 7‑6 PPO data formats
PKW Data
PKW data is used by the master to read/write to a single parameter of the AC drive.
The communication address of the AC drive parameter is directly determined by the
communication data. The functions of PKW data are as follows:
Reading function parameters of the AC drive
Modifying function parameters of the AC drive
Data format
PKW data consists of three groups of arrays, including the PKE, IND, and PWE. The
lengths of PKE and IND are two bytes, and the length of PWE is four bytes. The
following table describes the data format.
PKW Data Sent by the Master
Opera
tion
Com
mand
Parameter Address Reserved
Write: parameter
value
Read: null
PKE PKE IND IND PWE PWE PWE PWE
PKW Data Returned by the AC Drive
Opera
tion
Com
mand
Parameter Address Reserved
Successful: returned
value
Failed: error
information
PKE PKE IND IND PWE PWE PWE PWE
Data description