PROFIBUS DP Communication
‑155‑
7.6.2 Communication Control Parameters
Parameter Parameter
Name
Value Range Hexadecimal
Address
Decimal Address
U3‑16 Frequency
reference
Maximum
frequency to
+Maximum
frequency
Unit: 0.01 Hz
H7310 29456
U3‑17
Control
command
0001: Run in
forward direction
0002: Run in
reverse direction
0003: Jog in
forward direction
0004: Jog in
reverse direction
0005: Coast to stop
0006: Decelerate to
stop
0007: Reset upon
fault
H7311 29457
U3‑18
DO control
Bit0: DO1 output
control
Bit1: DO2 output
control
Bit2: Relay 1
output control
Bit3: Relay 2
output control
Bit4: FMR output
control
Bit5: VDO1
Bit6: VDO2
Bit7: VDO3
Bit8: VDO4
Bit9: VDO5
H7312 29458
U3‑19
AO1 control
0 to 7FFF,
indicating 0% to
100%
H7313 29459
U3‑20
AO2 control
0 to 7FFF,
indicating 0% to
100%
H7314 29460
U3‑21
FMP control
0 to 7FFF,
indicating 0% to
100%
H7315 29461
U3‑23
Speed control Signed data, 1 RPM
H7317 29463